APOGEE, TALON: Stack-based buffer overflow in web service enables denial of service

CVE-2026-102076High 8.7

← All vulnerabilities

Summary

Siemens APOGEE MBC/MEC (PPC), APOGEE PXC Compact and Modular, and TALON TC Compact and Modular building controllers contain a stack-based buffer overflow (CWE-121) in the upload handling of their web service. An unauthenticated remote attacker can send crafted input over the network to crash the affected device and cause a denial of service. Only availability is affected; the CNA rates confidentiality and integrity as not impacted.

Affected

  • APOGEE MBC (PPC) and MEC (PPC), BACnet and P2 Ethernet: all versions
  • APOGEE PXC Compact and Modular, BACnet: all versions below V3.5.7
  • APOGEE PXC Compact and Modular, P2 Ethernet: all versions below V2.8.21
  • TALON TC Compact and Modular, BACnet: all versions below V3.5.7

Fixed in

  • APOGEE PXC Compact and Modular, BACnet: V3.5.7 or later
  • APOGEE PXC Compact and Modular, P2 Ethernet: V2.8.21 or later
  • TALON TC Compact and Modular, BACnet: V3.5.7 or later (as listed in the advisory; verify in the full advisory)
  • APOGEE MBC/MEC (PPC): no fix known from the sources; check the Siemens advisory
  • Firmware is obtained via the Siemens partner portal.

Workaround

  • Disable the FTP/Web service on the affected devices. Siemens notes it is disabled by default on APOGEE, Desigo and TALON products.
  • Check first whether BACnet web pages or remote management depend on the service.
  • Segment the controllers and place them behind properly configured gateways or firewalls.

Exploitation

  • No evidence of exploitation in the wild found. CISA ADP Vulnrichment does not mark the CVE as known exploited.
  • No public proof-of-concept found.
  • Market estimate of exploit price by VulDB (USD 5k-25k) is not evidence of use.
  • The CVSS 4.0 score is 8.7 in the CNA record, while the Siemens advisory lists 8.8.

Our recommendation

  • Inventory all APOGEE, TALON and PXC controllers and their firmware versions, including P2 Ethernet and BACnet variants.
  • Confirm that none of the controllers are reachable from the internet or from untrusted networks.
  • Disable the FTP/Web service where operations allow it.
  • Plan the firmware update to V3.5.7 or V2.8.21 where a fix exists, and follow the Siemens advisory for APOGEE MBC/MEC.
  • Monitor the building automation network for unusual traffic and device restarts.

Public exploits

PoC-in-GitHub, Metasploit and Exploit-DB list nothing for this CVE.

Research sources

Researched and written up in English and German by an AI (Claude by Anthropic) based on NVD, CISA, EPSS and the sources listed. The vendor information is authoritative. Researched on 1 Nov 2026, 04:37.

Original description (NVD)

A vulnerability has been identified in APOGEE MBC (PPC) (BACnet) (All versions), APOGEE MBC (PPC) (P2 Ethernet) (All versions), APOGEE MEC (PPC) (BACnet) (All versions), APOGEE MEC (PPC) (P2 Ethernet) (All versions), APOGEE PXC Compact (BACnet) (All versions < V3.5.7), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.21), APOGEE PXC Modular (BACnet) (All versions < V3.5.7), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.21), TALON TC Compact (BACnet) (All versions < V3.5.7), TALON TC Modular (BACnet) (All versions < V3.5.7). The affected product web service does not properly validate user-supplied input in upload code. This could allow an unauthenticated remote attacker to cause a denial of service.

NVD references (1)

Sources

The tracker combines official, freely usable data sources – updated continuously:

This product uses data from the NVD API but is not endorsed or certified by the NVD. EPSS data © FIRST.org.

Affected? We can help.

We check whether your systems are affected, install updates and close the gap – continuously with the System Health Checker if you wish.